What to do about resonance in a 10kV unloaded busbar

Resonance in a 10kV unloaded busbar can be mitigated by detuning capacitor banks, installing harmonic suppressors, or applying active filtering to prevent overvoltages and equipment damage.

Understanding the Problem

Resonance occurs when the inductance of the system and the capacitance of connected devices (like capacitor banks or voltage transformers) interact at a specific frequency, amplifying voltage or current. In an unloaded busbar, the lack of load can make the system more susceptible to ferroresonance, leading to overvoltages, insulation stress, and potential failure of voltage transformers or fuses . Symptoms include unusual voltage spikes, blown fuses, or erratic grounding indications.

Practical Mitigation Strategies

1. Detuning Capacitor Banks

  • If the busbar has capacitor banks, series reactors can be added to shift the natural frequency away from harmonic frequencies. This creates a detuned capacitor bank, preventing resonance at common harmonic orders (e.g., 5th or 7th) and reducing overcurrent through the capacitors .

2. Harmonic Suppressors / Neutral Point Absorbers

  • Installing a neutral point harmonic absorber or detuning resistor at the neutral of transformers can dampen ferroresonance. These devices limit overvoltages, reduce current peaks, and stabilize the busbar voltage, protecting voltage transformers and extending equipment life .

3. Active Harmonic Filtering

  • An Active Harmonic Filter (AHF) can detect harmonic currents and inject counter-phase currents to cancel them. This method is effective when resonance is caused by harmonic contamination from non-linear loads or long cable runs .

4. System Configuration Adjustments

  • In some cases, changing transformer taps, regrouping loads, or avoiding certain switching operations can reduce the likelihood of resonance. However, these are often less effective than detuning or filtering .
Key Recommendations
  • Conduct a power quality measurement and resonance analysis to identify the resonant frequency and affected harmonics.
  • Avoid adding capacitors blindly, as this can exacerbate resonance.
  • Ensure that any mitigation device (detuned reactors, harmonic suppressors) is properly rated for 10kV operation.
  • Consider simulation studies for complex or newly designed busbars to predict resonance before installation.

By combining detuning, harmonic suppression, and careful system design, resonance in a 10kV unloaded busbar can be effectively controlled, preventing overvoltages, equipment damage, and operational disruptions .

What to do about resonance in a 10kV unloaded busbar

Study on ferromagnetic resonance characteristics and suppression

Ferromagnetic resonance often occurs in distribution networks with ungrounded neutral points due to transient

Calculation and simulating experiment on effectiveness of anti

In order to investigate the characteristics of ferroresonance and the effectiveness of anti-ferroresonance methods in

Analysis and Measures of 10kV Bus PT Breakdown Accident

Abstract: A 10kV bus PT breakdown accident caused by two-phase grounded is mainly introduced in this paper. Firstly, the bus

Research on the mechanism and restraining measures of

The results show that when eliminating the single-phase ground fault, it is easy to cause the frequency division

Practical solutions for preventing or damping ferroresonance

Ferroresonance is a non-linear resonance phenomenon that can affect power networks. The abnormal rates of

Study on ferromagnetic resonance characteristics and suppression

This article analyzes the principle and suppression measures of ferromagnetic resonance in electromagnetic voltage transformers.

Ferromagnetic Resonance Overvoltage Study and Suppression

In recent years, many scholars have conducted research on the resonance overvoltage of traditional 10 kV

Comparative study on ferroresonance elimination measures in 10kV

Four countermeasures are proposed to effectively avoid the occurrence of ferromagnetic resonance by destroying its

Case study: Failure of a transformer & switchgear buses due to a

We describe the power system and associated protection, the failure mechanism, the ferroresonance phenomenon,

The ferroresonance of 10kV distribution PT during live working

Based on this, a ferroresonance model in 10kV isolated neutral electrical system is established, and simulation is

Experimental research of dynamic vibration damping for rigid

To determine the optimal parameters of dynamic vibration dampers, their calculation was performed, taking into account the joint

Busbar protection schemes for distribution substations

Precision and reliability are important factors when designing a busbar protection scheme.

Coordination and protection of busbar distribution

In order to take account of busbar trunking thermal overload protection, the various protection switchgear technologies and the

Continuous non-invasive resonance detection in residential low

This paper presents the application of a new continuous non-invasive harmonic resonance detection technique for

Research on the mechanism and restraining measures of

In order to monitor the three-phase voltage of the busbar to ground, the substation bus is usually connected to the

Harmonic voltage results in MV busbar # 1

Download scientific diagram | Harmonic voltage results in MV busbar # 1 from publication: Harmonic distortion analysis on the MV

Main Effects of Harmonics in Electrical Installations

Effects of harmonics – Resonance The simultaneous use of capacitive and inductive devices in distribution networks

Temporary Overvoltages in Power Systems

Summary Temporary overvoltages (TOVs) are undamped or little damped power-frequency overvoltages of relatively long duration

How to Design Busbar Systems for Substations

Learn how to design efficient substation busbar systems with calculations, examples, and best practices.

Effective Busbar Maintenance and Repair Methods

Regular busbar maintenance and repair are crucial for ensuring the safe operation, efficient performance, and

Top Busbar Protection Issues That Worry Protection Engineers

A busbar protection must be capable of clearing all phase-to-earth faults, and in the case where they can occur, phase

(PDF) Understanding ferroresonance

This paper analyses ferroresonance and subsequent sustained parallel resonance that occurred during Finnish power

Transformer Resonance: Reasons, Modeling Approaches, Solutions

Due to the extension of the power grid with many complex and compact pieces of power equipment, transformers will

Study of Transformer Resonant Overvoltages Caused by

Case 4) Capacitor bank energization. If a capacitor bank is switched to a busbar which is connected to the highvoltage side of an

Vibration Analysis and Experimental Study of GIS Busbar Enclosure

The vibration mode was obtained by finite element technology. Accordingly, the vibration response of the busbar enclosure was

(PDF) Harmonic distortion analysis on the MV and LV distribution

Conclusion followed by the 7th, the 11th, the 3rd and the 13th. Harmonic distortion problem was being caused by The harmonic

Ferromagnetic Resonance Overvoltage Study and Suppression

This paper establishes the PT resonance circuit and clarifies its ferromagnetic resonance overvoltage mechanism. It

Harmonic Resonance in Power Systems – Voltage Disturbance

The difference between series and parallel resonance in power system is that series resonance creates a low

Examples of Ferroresonance in a High Voltage Power System

Concerns for ferroresonance in open-delta PTs exist: during energization of the unloaded stepdown transformer following interruption

Numerical analysis on the short‐circuit withstanding performance

Abstract: The short-circuit withstanding performance of busbar system is one of the most important safety indexes for low- voltage

Experimental research of dynamic vibration damping for rigid

To determine the optimal parameters of dynamic vibration dampers, their calculation was performed, taking into account the joint

Busbar protection schemes for distribution substations

Precision and reliability are important factors when designing a busbar protection scheme.

Coordination and protection of busbar distribution

In order to take account of busbar trunking thermal overload protection, the various protection switchgear technologies and the

Continuous non-invasive resonance detection in residential low

This paper presents the application of a new continuous non-invasive harmonic resonance detection technique for

Research on the mechanism and restraining measures of

In order to monitor the three-phase voltage of the busbar to ground, the substation bus is usually connected to the

Harmonic voltage results in MV busbar # 1

Download scientific diagram | Harmonic voltage results in MV busbar # 1 from publication: Harmonic distortion analysis on the MV

Study on ferromagnetic resonance characteristics and suppression

On the basis of theoretical analysis of the mechanism of ferromagnetic resonance, this paper uses electromagnetic transient

Parallel Resonance

Parallel resonances are associated with high impedances and the circulation of the harmonic currents in the parallel resonance

BUSBAR PROTECTION

Busbar protection may simultaneously trip a number of bus segments or even an entire busbar of a substation and the fast

Principles and applications of busbar protection schemes (you

A second line of defence is considered good practice in most schemes of busbar protection, not to give security

Main Effects of Harmonics in Electrical Installations

Effects of harmonics – Resonance The simultaneous use of capacitive and inductive devices in distribution networks

Temporary Overvoltages in Power Systems

Summary Temporary overvoltages (TOVs) are undamped or little damped power-frequency overvoltages of relatively long duration

How to Design Busbar Systems for Substations

Learn how to design efficient substation busbar systems with calculations, examples, and best practices.

Effective Busbar Maintenance and Repair Methods

Regular busbar maintenance and repair are crucial for ensuring the safe operation, efficient performance, and

Study on ferromagnetic resonance characteristics and suppression

Ferromagnetic resonance often occurs in distribution networks with ungrounded neutral points due to transient

Calculation and simulating experiment on effectiveness of anti

In order to investigate the characteristics of ferroresonance and the effectiveness of anti-ferroresonance methods in

Analysis and Measures of 10kV Bus PT Breakdown Accident

Abstract: A 10kV bus PT breakdown accident caused by two-phase grounded is mainly introduced in this paper. Firstly, the bus

Research on the mechanism and restraining measures of

The results show that when eliminating the single-phase ground fault, it is easy to cause the frequency division

Practical solutions for preventing or damping ferroresonance

Ferroresonance is a non-linear resonance phenomenon that can affect power networks. The abnormal rates of

Study on ferromagnetic resonance characteristics and suppression

This article analyzes the principle and suppression measures of ferromagnetic resonance in electromagnetic voltage transformers.

Ferromagnetic Resonance Overvoltage Study and Suppression

In recent years, many scholars have conducted research on the resonance overvoltage of traditional 10 kV

Comparative study on ferroresonance elimination measures in 10kV

Four countermeasures are proposed to effectively avoid the occurrence of ferromagnetic resonance by destroying its

Case study: Failure of a transformer & switchgear buses due to a

We describe the power system and associated protection, the failure mechanism, the ferroresonance phenomenon,

The ferroresonance of 10kV distribution PT during live working

Based on this, a ferroresonance model in 10kV isolated neutral electrical system is established, and simulation is

Study on ferromagnetic resonance characteristics and suppression

Ferromagnetic resonance often occurs in distribution networks with ungrounded neutral points due to transient

Calculation and simulating experiment on effectiveness of anti

In order to investigate the characteristics of ferroresonance and the effectiveness of anti-ferroresonance methods in

Analysis and Measures of 10kV Bus PT Breakdown Accident

Abstract: A 10kV bus PT breakdown accident caused by two-phase grounded is mainly introduced in this paper. Firstly, the bus

Research on the mechanism and restraining measures of

The results show that when eliminating the single-phase ground fault, it is easy to cause the frequency division

Practical solutions for preventing or damping ferroresonance

Ferroresonance is a non-linear resonance phenomenon that can affect power networks. The abnormal rates of

Study on ferromagnetic resonance characteristics and suppression

This article analyzes the principle and suppression measures of ferromagnetic resonance in electromagnetic voltage transformers.

Ferromagnetic Resonance Overvoltage Study and Suppression

In recent years, many scholars have conducted research on the resonance overvoltage of traditional 10 kV

Comparative study on ferroresonance elimination measures in 10kV

Four countermeasures are proposed to effectively avoid the occurrence of ferromagnetic resonance by destroying its

Case study: Failure of a transformer & switchgear buses due to a

We describe the power system and associated protection, the failure mechanism, the ferroresonance phenomenon,

The ferroresonance of 10kV distribution PT during live working

Based on this, a ferroresonance model in 10kV isolated neutral electrical system is established, and simulation is

Technical note

This reference is intended for preliminary specialty-cable research. Compatibility, link budgets, fire performance, installation methods, test limits and applicable standards must be verified for the specific project.

Still Have a Technical Question?

Use the inquiry form to describe a specialty cable route, fire requirement or testing question.

Start an Inquiry